iSN-104: four-channel Modbus RTU leakage detection module

03 February 2023 Product News

ICP DAS has unveiled a new liquid leak detection module iSN-104 which features 4 channels for connecting sensors and support for the Modbus RTU industrial protocol, which allows you to organize a liquid leakage detection and alarm system at industrial and domestic facilities, warehouses, pipelines and tanks. When a leak or cable break is detected on the iSN-104 module, the indicator lights up, the audible alarm signal turns on and the state of the Modbus RTU registers changes.


The iSN-104 module is an evolution of the iSN-101 single-channel model. iSN-104 can connect sensor cable or water level sensor.

Leak detection cable

Water-sensing cable сan detect a leak over a large area.


The iSN-104 can be connected to a cable with a break detection function and can be extended up to 500 meters, or a fixed length cable without a break detection function. Connection options are shown in the table:

Functions Connecting cable Leak sensor cable Terminal resistor
No cable break detection. Can't be extended. iSN-104-2.png
CA-LLD-EC-L030 – 3 m
iSN-104-4.png
CA-LLD-DC100-L010 – 1 m
CA-LLD-DC100-L030 – 3 m
CA-LLD-DC100-L100 – 10 m
CA-LLD-DC100-L300 – 30 m
CA-LLD-DC100-L500 – 50 m
No
There is a definition of a cable break. Can be extended up to 500 meters. iSN-104-5.png
CA-LLD-DC100X-L010 – 1 m
CA-LLD-DC100X-L030 – 3 m
CA-LLD-DC100X-L100 – 10 m
CA-LLD-DC100X-L300 – 30 m
CA-LLD-DC100X-L500 – 50 m
iSN-104-6.png
CA-LLD-DC100X-TR

Broken wire detection function is available for modules with the latest firmware.

Water level sensor

Water level sensor with stainless steel contacts allows you to determine the moment the liquid reaches the required level and respond to this event in time.

Water level sensor.jpg

Key features of liquid leak detection modules:

Model name iSN-101 iSN-104 iSN-104-E
Availability to order Available In developing
Protocol Modbus RTU or DCON Modbus TCP
Connection interface 1x RS-485 1x 10/100 Base-TX, RJ-45
Channels 1 4
Relay Yes
Power requirements 10…30 V DC 10…48 V DC
PoE Yes, IEEE 802.3af Class 1
Power consumption 1.5 W 1.6 W
Dimensions, mm 83 x 70 x 29 72 x 95 x 57
Operational temperature -25…+75 °C

Fast Product Request